Hydrant flow test calculator
Enter the static and residual pressure from the test hydrant and the pitot reading from each flowing outlet. You get the flow during the test, the flow available at 20 psi residual, and the hydrant's NFPA 291 color class. It runs in your browser and nothing is saved.
Checked October 24, 2026
Figure it at a residual other than 20 psi
Available flow at 20 psi residual
Enter the static, the residual and the flow. The answer shows here as you type.
WatchRoom does this math on every flow test your crew logs, keeps each hydrant's history, and colors the map by class. See hydrants in WatchRoom
How a hydrant flow test works
A flow test uses two hydrants on the same main. The test hydrant carries a pressure gauge on a cap. The flow hydrant is the one you open, usually the next hydrant downstream.
- Put a gauge on the test hydrant, open it, bleed the air and read the static pressure with no water moving.
- Open one or more outlets on the flow hydrant all the way. Hold a pitot gauge in the center of each stream, about half the outlet's diameter out from the opening, and read the pitot pressure once the needle steadies.
- At the same time, read the residual pressure on the test hydrant while the water is flowing.
- Close the flow hydrant slowly. Shutting it fast sends a pressure surge back through the main.
- Write down the outlet size and shape for each flowing outlet. The calculator needs both.
If the residual barely moved, the main has more water than you drew. Open another outlet or a second flow hydrant and read again, until the pressure drops at least 25 percent from static.
Reading a flow gauge with GPM and PSI on one dial
Many departments flow with a gauge made for one outlet or diffuser that shows two scales on the same face: pressure in psi, usually in black, and the flow that pressure means for that outlet, in gpm, usually in blue. The needle points at both at once, so the crew reads the flow straight off the dial instead of working it out from a pitot reading.
That dial measures the water leaving the flow hydrant. Its psi is the pressure in the stream, not the residual. The residual still comes from the gauge on the test hydrant, read while the water is flowing. Write down all three: the static and residual from the test hydrant, and the gpm from the flow gauge.
With those three, the flow at 20 psi follows from the formula below. WatchRoom does that math for you when a flow test is logged: type the gpm from the dial as the flow, the static and the residual, and the record shows the flow at 20 psi and the hydrant's color class. A test logged with no residual keeps the flow you measured and leaves the 20 psi number blank rather than guess it.
The formulas (NFPA 291)
The flow out of each open outlet comes from its pitot reading:
The coefficient depends on how the outlet meets the barrel: 0.90 for a smooth, rounded outlet (most hydrants), 0.80 for a square, sharp one, and 0.70 for an outlet that sticks into the barrel. A 2.5 inch outlet with a rounded edge reading 25 psi flows about 839 gpm. With several outlets open, add the flows together.
Then the flow available at 20 psi residual comes from the pressures:
With 80 psi static, 60 psi residual and 839 gpm flowing, the hydrant can deliver about 1,518 gpm before the main drops to 20 psi. That makes it Class AA.
NFPA 291 hydrant color codes
NFPA 291 rates each hydrant by its flow at 20 psi residual and marks the class by painting the bonnet and caps. Crews read the color and know what the hydrant will give before they lay a line.
| Class | Bonnet color | Rated flow at 20 psi |
|---|---|---|
| Class AA | Light blue | 1,500 gpm or more |
| Class A | Green | 1,000 to 1,499 gpm |
| Class B | Orange | 500 to 999 gpm |
| Class C | Red | Under 500 gpm |
Why the answer is figured at 20 psi
While the fire department draws water, the water system is normally expected to keep at least 20 psi in the main. Rating every hydrant at that same residual puts them all on the same footing, which is why NFPA 291's classes and ISO's water supply review both use it. If you need the flow at another pressure, the calculator takes any residual under "Figure it at a residual other than 20 psi".
What ISO looks at
Water supply is 40 of the 100 points in an ISO grading. Part of that credit is for the hydrants themselves: how much they flow, how they are spaced, and whether they are inspected every year and flow tested on a five-year cycle. ISO credits records, so a test nobody wrote down counts as a test that never happened. The ISO rating guide covers the rest of the score.
Questions chiefs ask
How do you calculate gpm from a pitot reading?
NFPA 291 uses Q = 29.83 x c x d squared x the square root of p, where d is the outlet diameter in inches, p is the pitot reading in psi, and c is the outlet coefficient (0.90 for a smooth, rounded outlet, the usual case). A 2.5 inch outlet reading 25 psi flows about 839 gpm.
Why is hydrant flow figured at 20 psi residual?
20 psi is the lowest residual pressure the water system is normally expected to keep while the fire department draws from it. Rating every hydrant at 20 psi puts them all on the same footing, and it is the number NFPA 291's color classes and ISO's water supply review use.
How much should the pressure drop during a flow test?
NFPA 291 asks for at least a 25 percent drop from static to residual. With less, a small error in either gauge reading swings the answer a lot. Open more outlets or another hydrant until the residual falls far enough.
What do the colors on a hydrant bonnet mean?
Under NFPA 291 the bonnet and caps show the rated flow at 20 psi: light blue for 1,500 gpm or more (Class AA), green for 1,000 to 1,499 (Class A), orange for 500 to 999 (Class B), and red for under 500 (Class C).
How often do hydrants need to be flow tested for ISO?
ISO gives credit for hydrant inspections and flow tests on a schedule: inspections every year, and flow tests on a five-year cycle for full credit, with less credit the longer it has been. Records of each test are what get credited.
Keep the records once, use them everywhere
In WatchRoom the crew logs a flow test from a phone at the hydrant: static, residual and pitot go in, the gpm and class come out with the same math as this page, and each hydrant keeps its full history on a map colored by class. The inspection and flow test dates roll straight into the ISO estimate.